The APC Back-UPS 500VA, 230V, AVR, IEC Sockets backup power supply provides backup power during a power outage, protection against surges and spikes, and data line protection (e.g., Ethernet), and is designed for indoor use. LED and audio signals indicate mains operation, battery operation, low battery, overload, overheating, battery replacement needed, and charger failure.
Safety instructions:
Connect only to an earthed socket.
Do not use in damp or dusty environments.
Do not open the battery (toxic electrolyte).
Risk of electric shock, burns from short circuits, or explosion if mishandled.
Do not use metal objects when working with the battery and wear protective equipment.
Installation and use:
Placement: away from sun, heat, moisture, and dust, ideally on the floor.
Procedure: connect the battery, plug in your devices (without an extension lead), plug the UPS into a socket, switch it on with the button.
Do not plug into a surge protector or an extension lead.
Maintenance and service:
The battery is not normally user-replaceable.
Technical specification:
Dimensions (H × W × D): 138 × 98 × 310mm
Weight: 4.2kg
Colour: black
Mounting: Tower (freestanding)
Operating temperature: 0 to 40°C
Storage temperature: -15 to 40°C
Humidity (operating and storage): 0–95% (non-condensing)
IP rating: IP20
Noise level: approx. 40dBA
Certification: CE, EAC
Standards: EN/IEC 62040-1:2019/A11:2021, EN/IEC 62040-2:2006/AC:2006, EN/IEC 62040-2:2018
Performance and power:
Rated power: 500VA / 300W
Maximum configurable power: 500VA / 300W
Input voltage: 230V AC (1 phase)
Output voltage: 230V AC (1 phase)
Input voltage range: 140–300V
Mains frequency: 50/60Hz ±5% (auto-sensing)
Output frequency: 50/60Hz ±1Hz (sync to mains)
Power factor (cos φ): 0.63
Topology: Standby (offline)
Waveform type: stepped approximation to a sinewave
Transfer time: 6ms typical, 10ms max
Connectivity and interfaces:
Input connector: IEC 60320 C14
Input type: IEC 60320 C13
Output sockets: 3× IEC 60320 C13
USB compatibility: yes
Cable length: 1.5m
Battery and runtime:
Battery type: lead-acid
Capacity: 7.0Ah
Battery voltage: 12V
Typical recharge time: 8 hours
Battery life: 3–5 years
Runtime at full load (300W): approx. 1 min
Runtime at half load: approx. 7 min 15 s
Operating time (range): 30–300W → approx. 1 min 2 s at max load
Protection:
Surge energy rating: 273J
Indication: LED (online / on battery)
Schneider Electric IT Logistics Europe Limited City East Business Park, Ballybrit Galway, Ireland, [email protected], +19789304141
Specifications can be changed without notice. Images are for illustrative purposes only.